Permit Number: T22CM05249
Parcel: 12111172C

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM05249
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2022 PAUL CAMARENA ZONING REVIEW Reqs Change FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM05249
Addition
1627 N MOUNTAIN VIEW AV Zoning R-1

TRANSMITTAL DATE:? July 19, 2022


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: Clearly show everything on site. Based on current aerial photos there ar three possible unpermitted shed on the rear portion of the property. Provide permit documentation for the sheds or include them in this submittal. (Square footage, height and building setbacks) Additional comments may be forth coming.

2.COMMENT: Draw dimension and label the height of the new structure measured from design grade to top of wall.




If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
07/19/2022 PCAMARE1 ENGINEERING REVIEW Passed
07/29/2022 AWARNER1 NPPO REVIEW Approved
07/30/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05249


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Update the structural design notes on sheet 2 to indicate a basic designed wind speed of 115 mph and a seismic category B. 2018 IRC table R301.2(1) as amended.
2. Indicate if the existing headers will remain for the new openings from the existing house to the new addition or if they will be replaced.
3. Indicate how the new foundation will be tied into the existing such as with rebars or other suitable method.
4. Indicate that the soil under the slab and around the footings will be treated for termites prior to the pouring of the concrete. 2018 IRC R318.


BUILDING REVIEW COMMENTS:
Denied1. Indicate the required window energy requirements on the drawings. Windows are required to have a minimum U factor of .40 and a SHGC of .25. 2018 IECC table R402.1.2.
2. Indicate on the drawings that fireblocking will be installed to cut off both vertical and horizontal concealed draft openings between stories and attic or roof area. 2018 IRC R302.11.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Denied
1. Note on the drawings that the new can lighting installed in the ceiling will be IC rated and sealed for energy efficiency requirements. 2017 NEC 410.66.
2. Note that all new outlets installed in bedrooms, living rooms, family rooms, dens, hallways, and similar areas will be ARC fault protected. 2017 NEC 210.12.
3. Note that a minimum of 90% of all lighting fixtures in the dwelling will contain high-efficacy lamps. 2018 IECC R404.1.
4. Note that all new or replaced 15- and 20-amp outlets shall be tamper proof type. 2017 NEC 210.52.
5. Indicate a smoke detector in the other existing bedroom and in the hallway outside of the bedroom doors. Smoke detectors shall be installed in each sleeping room, outside of each sleeping room in the immediate vicinity of the bedroom. 2018 IRC R314.2.
6. Note on the drawings that all smoke detectors shall receive their primary power from the building wiring with a battery backup and shall be interconnected so that the actuation of one alarm will activate all. 2018 IRC R314.4.
7. Note on the drawings that the carbon monoxide device shall receive their primary power from the building wiring with a battery backup and shall be interconnected so that the actuation of one alarm will activate all. 2018 IRC R314.4. Smoke detectors and carbon monoxide alarms may be combined.


PLUMBING REVIEW COMMENTS:
Conditionally Approved
No plumbing work has been included in this submittal


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov