07/18/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05173

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
Provide Structural connection details supported with pertinent calculations.

BUILDING REVIEW COMMENTS:
Denied
1. Please provide a fence around the ground supported-proposed PV solar system.
2. Please confirm a separate permit will be applied for the foundations and the structure upon which the PV installation is proposed. Otherwise provide the pertinent details for review along-with the revised permit application stating the increased scope of work and the revised evaluation.
3. Provide structural connection details

MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov