The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T22CM05163
Parcel: 12507400A

Address:
2500 E 6TH ST

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM05163
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05163

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Sheet G-1: Provide the existing area of the space in the scope of work.
2. Sheet G-1: The occupant load for the dining area is calculated incorrectly. Counting available seats is not the proper way to determine occupant loads. Provide a corrected occupant load in accordance with Table 1004.5.
3. Sheet G-2: It appears that means of egress continuity would be impeded for egress. Show the location of the clear egress paths throughout the restaurant in accordance with Section 1003.6 and 1005.
4. Sheet A-2: There is an insufficient amount of exit signage provided. Show the location of all exit signage in accordance with Section 1013.
5. Sheet A-2: There is an insufficient of egress illumination provided. Provide the location of all egress illumination in accordance with Section 1008.
6. General: Provide clarification on any adjacent tenants to ensure proper separation between tenants.
7. General: At least 5% of the dining surfaces are required to have mobility features. Provide calculations of the required amount of accessible seating and indicate the locations. Additionally, ensure that surfaces are properly dispersed throughout the structure. Section 226.1 and 226.2 of the 2010 ADAAG.
8. General: Provide within the plans, drawings that clearly indicate the accessible routes within the space that are in accordance with Section 206.2.5.
9. General: Provide within the site plans, drawings that clearly indicate the accessible routes within the site and site arrival points that connect the accessible parking to the accessible entrances that are in accordance with Section 206.2.1 and 206.2.2.


MECHANICAL REVIEW COMMENTS:
Denied
1. Sheet M-1: There is a portion of the plan that has been blocked out and is not able to be reviewed. Provide the area that has been blocked for review.
2. Provide evidence that the existing hood is sized properly and meets all current code requirements for the new equipment being used for this project.


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/28/2022 SSHIELD1 ENGINEERING REVIEW Passed
07/28/2022 STEVE SHIELDS ZONING REVIEW Approved
07/28/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/08/2022 ROBERT SHERRY WATER REVIEW Completed
08/15/2022 JVINCEN1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/15/2022 NGARCIA3 OUT TO CUSTOMER Completed