Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM05159
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/22/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM05159 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied See review comments noted under Building review BUILDING REVIEW COMMENTS: Denied 1. Please show dimensions of the fire-access pathway shown on the roof plan. 2. IRC Section 324.6.2 requires a minimum of 18 inches wide pathway on both sides of the ridgeway if the solar area is less than 33% of the roof area, please provide area calculations, show pathway on both sides of the ridge as only on one side is shown and show the width of the pathway on the roof plan. 3. Please confirm if 4x6 at 24 inches on center shown in the detail is existing roof framing or is it new proposed framing? 4. The structural layout for panel A is provided, where is the structural layout for panels B and C?d MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 09/04/2022 | ARUIZ1 | OIP | REVIEW | Completed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/05/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |