Review Date Reviewer's Name Type of Review Description Status Comments
07/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05159

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
See review comments noted under Building review


BUILDING REVIEW COMMENTS:
Denied
1. Please show dimensions of the fire-access pathway shown on the roof plan.
2. IRC Section 324.6.2 requires a minimum of 18 inches wide pathway on both sides of the ridgeway if the solar area is less than 33% of the roof area, please provide area calculations, show pathway on both sides of the ridge as only on one side is shown and show the width of the pathway on the roof plan.
3. Please confirm if 4x6 at 24 inches on center shown in the detail is existing roof framing or is it new proposed framing?
4. The structural layout for panel A is provided, where is the structural layout for panels B and C?d


MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
09/04/2022 ARUIZ1 OIP REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/05/2022 NGARCIA3 OUT TO CUSTOMER Completed