Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM05149
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/14/2022 | IMONSHI1 | ZONING | REVIEW | Reqs Change | FROM: Iman Monshizadeh PDSD Zoning Review Section PROJECT: T22CM05149 / Porch addition Plot Plan Review (1st Review) 5362 E Rosewood / R-2 Zone TRANSMITTAL DATE: 07/14/2022 Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1.COMMENT: Provide a complete site plan on the next submittal. An example plot plan that shows all required information can be found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf. This shall in include: a. Lot coverage calculation that meets the requirements of UDC Article 6.4.3 & the example shown on the residential plot requirements. b. setback dimensions from structure to property lines. c. Property line distances d. Zoning of adjacent parcels. For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp |
| 07/14/2022 | IMONSHI1 | ENGINEERING | REVIEW | Passed | |
| 07/14/2022 | IMONSHI1 | NPPO | REVIEW | Passed | |
| 07/26/2022 | KEN VAN KARSEN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T22CM05149 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL REQUIREMENTS: The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans. Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits SITE PLAN: 1. Indicate the location of buildings and any utilities supporting or effecting the proposed structure. FOUNDATION PLAN: 1. Dimension the footing length, width, and depth into undisturbed soil for each footing type and condition, R403.1. Show the minimum 12” reinforced footing depth below the undisturbed ground surface R403.1. Show #4 rebar reinforcement with 3” clearance from earth, R403.1.3.5.3. Provide ½” anchor bolts with 7” embedment, R403.1.6. FRAMING PLAN: 1. Provide a complete roof framing plan with beams and rafters sized with appropriate load carrying capacity, R301.1. 2x6 rafters may not be used as a beam. Show 4x8 beams. 2x4 rafters may not span 12’. Show 2x6 rafters. SECTIONS - DETAILS: 1. Show the Post Section Detail with #4 rebar in the footing, R403.1. 2. Notate and specify the size of post base with 1” standoff above concrete, R317.1.4 exception 1. 3. Show roof (uplift resistance) rafter fasteners (H2.5) with appropriate uplift capacity, R802.11 amended. 4. Show any ledger fasteners with stucco removal between wall studs and ledger. ELECTRICAL PLANS: 1. Show the overhead service conductor with an 8-foot clearance above the roof, E3604.2.1 or relocate the service panel from under the roof. The service line change or a new panel location must be coordinated with TEP for approval. Please contact the plans reviewer if you have any questions: Ken Van Karsen 520 837-4912 City of Tucson Residential Plan Review |