Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM05147
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/07/2022 | RPARSON1 | OIP | REVIEW | Completed | |
| 07/20/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM05147 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Provide structural evaluation of the roof framing to be able to support the ballasted weight system along-with the PV system as proposed. 2. Provide structural calculations to show proposed systems adequacy to resist the wind uplift loads. BUILDING REVIEW COMMENTS: Denied 1. Provide Fire-access pathways on the roof plan complete with their dimensions and clearances to the vents and other roof penetrations. 2. Provide area calculations for the proposed solar panels. 3. Provide structural evaluation of the roof framing to be able to support the ballasted weight system along-with the PV system as proposed. 4. Provide structural calculations to show proposed systems adequacy to resist the wind uplift loads. MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/20/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |