Permit Number: T22CM05138
Parcel: 136334450

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM05138
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2022 RPARSON1 OIP REVIEW Completed
07/20/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05138

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. From the roof plan it appears that new 15 PV solar modules are proposed in addition to few existing roof panels on the roof. Existing panels are not marked on the plans, please mark up the roof plan with existing and new installations for clarity.
2. In the revised calculations, while calculating the solar area on the roof, existing solar panel area also needs to be included in order to establish how much wide and where the fire-access pathway's are required.
3. Please mark up the roof plan with the fire-access pathways, legend shows two different pathways but there seems to be some information lacking since the location of the pathways on the roof could not be established based on information provided in the legend.


MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/20/2022 NGARCIA3 OUT TO CUSTOMER Completed