Permit Number: T22CM05128
Parcel: 136234090

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM05128
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2022 RPARSON1 OIP REVIEW Completed
07/20/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05128

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
Please see review comments entered under "Building".


BUILDING REVIEW COMMENTS:
Denied
1. Please show on the roof plan, code required fire-access pathways. What is shown lacks the dimensions, but guessing from the visual scale it seems what is provided does not conform to the code required minimum 36 inch wide pathways.
2. Please include calculations for the solar panel module layout and the roof area and include the slope of the existing roof in drawing detail.
3. Please provide structural details pertaining to the connection of the solar modules to the roof framing members.


MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/20/2022 NGARCIA3 OUT TO CUSTOMER Completed