Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM05128
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/07/2022 | RPARSON1 | OIP | REVIEW | Completed | |
| 07/20/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM05128 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied Please see review comments entered under "Building". BUILDING REVIEW COMMENTS: Denied 1. Please show on the roof plan, code required fire-access pathways. What is shown lacks the dimensions, but guessing from the visual scale it seems what is provided does not conform to the code required minimum 36 inch wide pathways. 2. Please include calculations for the solar panel module layout and the roof area and include the slope of the existing roof in drawing detail. 3. Please provide structural details pertaining to the connection of the solar modules to the roof framing members. MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/20/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |