Permit Number: T22CM05113
Parcel: 140261600

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM05113
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2022 RPARSON1 OIP REVIEW Completed
07/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05113


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide a lag bolt connection up-lift calculation demonstrating the wind load supporting capability. R301.
2. Provide sufficient standoffs for achieving a point load calculation under 45 lbs. Calculate the point loads. R301.1


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/22/2022 NGARCIA3 OUT TO CUSTOMER Completed