Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM05100
Parcel: 140322150

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM05100
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2022 RPARSON1 OIP REVIEW Completed
07/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05100


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide a lag bolt connection up lift calculation demonstrating the wind load supporting capability. R301.1
2. Show the size and total number and spacing of all lag bolts


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/22/2022 NGARCIA3 OUT TO CUSTOMER Completed