Review Date Reviewer's Name Type of Review Description Status Comments
07/23/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05081

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Sheet T1.0: The occupancy group listed is incorrect. A B-2 occupancy does not exist. Provide a corrected occupant group.
2. Sheet T1.0: The construction type is listed as V-N. This type of construction does not exits. Provide a corrected construction type.
3. Sheet A1.0: The occupant load for the waiting area is calculated incorrectly. The seating provided is not fixed seating and thus is not permitted to be counted. Provide a corrected occupant load in accordance with Table 1004.5.
4. Sheet A2.0: All of the corridors are required to have a one hour fire rating. Provide a properly rated corridors in accordance with Section 1020.1 and Table 1020.1 and update all door ratings located in the corridors walls in accordance with Section 716.
5. Sheet A2.2: There is an insufficient amount of exit signage. Provide additional exit signage in accordance with Section 1013.
6. General: Provide clarification on the adjacent tenants to ensure proper tenant separation.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Denied
1. Sheet D1.0: Show in demolition sheet all the electrical devices, equipment and fixtures in existing walls, partitions and ceiling to be demolished. Indicate if all conductors and raceways will be demolished back to the source.
2. Sheet E1.0: Dishwasher receptacle (A-26) installed within 6 ft from top inside edge of sink shall have ground fault protection for personnel. 2017 NEC, 210.8(B)(5).
3. Show detail / provide detail direction for firestopping back to back electrical boxes in fire rated walls within 24 inches of each other (HALL and BREAK ROOM). Alternately, separate back to back boxes in fire rated walls at least 24 inches. 2018 International Building Code 714.4.1.1.
4. Sheet E1.0: Provide at least one outlet in an accessible location at the entrance of the occupancy for sign or outline lighting system use. NEC 2017, 600.5(A).
5. Sheet E4.0: Current NEC code in effect for this jurisdiction is 2017, Electrical specification, number 1 calls for 2014 NEC code. (tucsonaz.gov).https://www.tucsonaz.gov/pdsd/building-codes
6. Sheet E1.0: Define each type of patient care space so that wiring methods can be evaluated in each of the patient care spaces. See definitions of patient care space in NEC 2017, article 517.
7. Sheet E2.0: Define each type of patient care space so that wiring methods can be evaluated. See definitions of patient care space in NEC 2017, article 517.
8. Sheet E2.0: Provide photometric calculation that emergency luminaires (Eb) can provide initial illumination not less than the value required in the IBC 2018, 1008.3.5 along the path of egress at floor level. IBC 2018, 1008.3.5.


PLUMBING REVIEW COMMENTS:
Denied
First Plumbing Review:
1). This occupancy type & load requires an high low drinking fountain, update all affected pages -IPC 403.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/26/2022 PCAMARE1 ENGINEERING REVIEW Passed
07/26/2022 PAUL CAMARENA ZONING REVIEW Approved
07/26/2022 PCAMARE1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/04/2022 ROBERT SHERRY WATER REVIEW Completed
09/01/2022 JVINCEN1 FIRE REVIEW Reqs Change resolve building comments