| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/06/2022 | VFLORES1 | PIMA COUNTY - ADDRESSING | PIMA COUNTY - ADDRESSING | Reqs Change | Please contact Pima County Addressing to have units added into the system Phone #:520-724-9512 Email: addressing@pima.gov |
| 07/11/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Revise the gas pipe sizes based on the demand and developed pipe length for each appliance. Verify the actual input of the AC units. The branch pipes to each AC unit are undersized and the main gas line to apartment D is undersized. Reference: Sections 402.1 and 402.3, IFGC 2018. 2. Show the sizes and the developed lengths of all the pipes serving the gas-fired appliances. Reference: Section 402.1, IFGC 2018. |