Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM05056
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/01/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. Please provide more detail as to conductor, conduit, sizes and types are being utilized (wiring methods) from the new service disconnect switches to the Term Cabinets. For example; Are the wireways (gutters) utilizing enclosed bussing, stand-offs with lugs, or individual sets of conductors for each service disconnect terminating in the Term Cabinet. Perhaps provide a detail that is typical for all the 200 amp and the one 100-amp service. Or continue the ‘SUITE PANEL FEEDERS’ detail all the way to the term cabinet. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/01/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |