Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM05054
Parcel: Unknown

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM05054
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Please provide more detail as to conductor, conduit, sizes and types are being utilized (wiring methods) from the new service disconnect switches to the Term Cabinets. For example; Are the wireways (gutters) utilizing enclosed bussing, stand-offs with lugs, or individual sets of conductors for each service disconnect. Perhaps provide a detail that is typical for all the 200 amp and the one 100-amp service. Or continue the ‘SUITE PANEL FEEDERS’ detail to the term cabinet.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/01/2022 VVERA1 OUT TO CUSTOMER Completed