Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T22CM05035
Parcel: 140420270

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM05035
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2022 JVINCEN1 FIRE REVIEW Approved
09/23/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM05035

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
Some details for the connection of RTU's and Water heater and the new roof openings is provided as a response on drawing A9.1. Seems like only a part of the whole detail is provided, it isn't clear from the submitted response, what is the weight/ size of the RTU's/ Water Heater considered in the design, how were the framing members and their connector sizes arrived at, was the existing framing evaluated for it being adequate and not requiring any structural upgrade because of the additional loads imposed by the roof supported units/ water heater?


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
Second Plumbing Review:
1). SAME-Dual lavatory fixture spacing details on plan page A6.0 are non compliant, lavs need 30" center to center separation & still maintain 15" sidewall clearance- -IPC 405.3.1 ** SEE Detail J**
2). OK
3). OK


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
09/29/2022 ROBERT SHERRY WATER REVIEW Completed