| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Coordinate the plumbing and mechanical designs. AC-1, AC-2, and AC-3 are called out as heat pumps in the mechanical design. |
| 07/19/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/20/2022 | IMONSHI1 | ZONING | REVIEW | Approved | |
| 07/20/2022 | IMONSHI1 | ENGINEERING | REVIEW | Passed | |
| 07/20/2022 | IMONSHI1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 07/21/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 07/27/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. |
| 08/01/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical review comments and provide a written response. 1. Provide compliance with the 2018 IECC for the lighting. 2. Include load calculations for the panel schedules and balance loads between phase as close as possible. Include total electrical service load for the building.NEC 408.3B Ref; 2018 IBC 107.2.1, 2017 NEC, 2018 IECC. |
| 08/19/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | Activity Number: T22CM05031 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. Sheet T1.1 Provide the following, Type of construction, Square footage, Occupancy Type, Occupant Load and scope of work. Sheet A2.1 Provide exit plan for Entire Building. Show Accessible path of travel to the public way and Accessible parking. Provide occupant load of each room. Sheet A2.1 How do you enter into the workout room? Sheet A2.2 Show expanded view of Accessible Stall Sheet A3.1 Is the Ceiling existing or is it new construction? Sheet A3.1 Show details of ceiling construction if any modifications are part of the scope of work. Sheet A5. Provide detail of Door Hardware showing compliance with ADAAG and IBC Chapter 10 If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |