Permit Review Detail
Review Status: Active
Review Details: RESUBMITTAL
Permit Number - T22CM05025
Review Name: RESUBMITTAL
Review Status: Active
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/14/2022 | ANY | ELECTRICAL-COMMERCIAL | REVIEW | Active | |
10/20/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The estimate of the scope of work is not adequate to obtain a permit to repair the fire damage. Provide drawings showing the plumbing fixtures that will be installed and specifications (e.g. fixture descriptions and manufacturer's model numbers) for those fixtures. If any piping (water supply, waste and vent piping) needs to be replaced, show that on the drawings. |
10/20/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The estimate of the scope of work is not adequate to obtain a permit to repair the fire damage. Provide drawings showing which new HVAC systems or equipment will be installed. New HVAC units will have to comply with Sections R403.1 and R503.1.2, IECC 2018 for efficiency, controls, and ductwork. |