Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM05025
Parcel: 11007087B

Review Status: Active

Review Details: RESUBMITTAL

Permit Number - T22CM05025
Review Name: RESUBMITTAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2022 ANY ELECTRICAL-COMMERCIAL REVIEW Active
10/20/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The estimate of the scope of work is not adequate to obtain a permit to repair the fire damage. Provide drawings showing which new HVAC systems or equipment will be installed. New HVAC units will have to comply with Sections R403.1 and R503.1.2, IECC 2018 for efficiency, controls, and ductwork.
10/20/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The estimate of the scope of work is not adequate to obtain a permit to repair the fire damage. Provide drawings showing the plumbing fixtures that will be installed and specifications (e.g. fixture descriptions and manufacturer's model numbers) for those fixtures. If any piping (water supply, waste and vent piping) needs to be replaced, show that on the drawings.