Permit Number: T22CM05025
Parcel: 11007087B

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM05025
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

The Code enforcement inspectors report states multiple units received water damage besides the fire damage..... The application for the permit is requesting power and gas to be restored to the undamaged units. Please specify which units need power restored and verify no water or fire damage occurred in these units

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
08/03/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Identify the apartments that are undamaged and require restoration of the natural gas service.
08/03/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/20/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/22/2022 NGARCIA3 OUT TO CUSTOMER Completed