4646 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM04999
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2022 WILDAN BUILDING-COMMERCIAL REVIEW Completed
09/19/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The revised design for the stormwater drainage now shows the primary roof drain discharging over an existing pedestrian circulation path (i.e. sidewalk). Primary rainwater leaders may not discharge onto a sidewalk. Reference: Section 7-01.4.1 E, Technical Standards Manual, Tucson Arizona Unified Development Code. [Initial comment: Detail 5/A2.0 calls for the new primary roof drain to connect to the existing underground storm sewer. What is the size and location of the existing storm sewer? Reference: Section 107.2.1, IBC 2018.]