Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM04999
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/14/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Completed | |
| 09/19/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The revised design for the stormwater drainage now shows the primary roof drain discharging over an existing pedestrian circulation path (i.e. sidewalk). Primary rainwater leaders may not discharge onto a sidewalk. Reference: Section 7-01.4.1 E, Technical Standards Manual, Tucson Arizona Unified Development Code. [Initial comment: Detail 5/A2.0 calls for the new primary roof drain to connect to the existing underground storm sewer. What is the size and location of the existing storm sewer? Reference: Section 107.2.1, IBC 2018.] |