Permit Number: T22CM04999
Parcel: Unknown

Address:
4646 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM04999
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Detail 5/A2.0 calls for the new primary roof drain to connect to the existing underground storm sewer. What is the size and location of the existing storm sewer? Reference: Section 107.2.1, IBC 2018.
07/19/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/19/2022 ROBERT SHERRY WATER REVIEW Completed
07/21/2022 JVINCEN1 FIRE REVIEW Approved
07/25/2022 WBERGER1 ZONING REVIEW Approved
07/25/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
07/26/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/19/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM04999

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Sheet T0.0; . S.I.C. for masonry and post installed anchors must be completed in entirety and include the approved agency and the registered design professional. If two different agencies are to be utilized, then separate S.I.C.s must be completed and submitted. DMA
Sheet S3.0; Tucson amendment to 2018 IBC Section 1609.5.1.1 (1) and (2)-2.1, 2.2 (2.2.2); Uplift resistance to microburst effects. Plans and calcs do not indicate these additional requirements. DMA
Sheet S3.1; Provide dimension of footings. DMA
Sheet S3.0; Tucson amendment to 2018 IBC Section 1609.5.1.1 (1) and (2)-2.1, 2.2 (2.2.2); Uplift resistance to microburst effects. Plans and calcs do not indicate these additional requirements. DMA
S.I.C.; Complete certificate in entirety. DMA


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/25/2022 SBLOOD1 ENGINEERING REVIEW Approved