Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM04994
Parcel: 12404102B

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL TI

Permit Number - T22CM04994
Review Name: 3RD PARTY REVIEW - COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/26/2022 PCAMARE1 ENGINEERING REVIEW Passed
07/26/2022 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/26/2022 STEVE SHIELDS ZONING REVIEW Approved
08/03/2022 ROBERT SHERRY WATER REVIEW Completed
08/11/2022 JPEELDA1 FIRE REVIEW Reqs Change Exiting shall comply with IFC 2018, Chapter 10, Section 1007.1.1
Exits may not go through a kitchen IFC 2018, Chapter 10, Section 1016.2 #5
Please add a note:
Fire sprinkler plans shall be submitted to and a permit obtained from TFD
Fire alarm plans shall be submitted to and a permit obtained from TFD
Kitchen fire suppression plans shall be submitted to and a permit obtained from TFD

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
Fire Plans Examiner
Tucson Fire Department
520-837-7033
09/16/2022 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Completed
09/16/2022 DBENOIT1 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/16/2022 VVERA1 OUT TO CUSTOMER Completed