Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM04989
Parcel: 13355230B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM04989
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2022 JVINCEN1 FIRE REVIEW Approved
10/06/2022 DBENOIT1 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04989

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
In this response only the gravity load capacity was addressed, structural evaluation for adequate Lateral Load carrying capacity after new opening in the wall was also required in the first set of review comments. Please address the lateral capacity of the wall being adequate after the new opening is made in the wall.

BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E-131 FLOOR PLAN - ETHERNET SYSTEM: No data drops for exam rooms?
E-631 PANEL SCHEDULES: No electrical issues, LCPR may need its feeder and 70 amp CB to be upgraded as it has a calculated 66-amp load.

PLUMBING REVIEW COMMENTS:
Denied
Second Plumbing Review: no response to comments
1). SAME-Lavatory Faucet on plan page P-630 needs to be the automatic type- Tucson Plumbing code amendment 419.6
2). SAME-Update detail #2 on P-630 to list ASSE 1070 mixing valve type- IPC 419.5
3). SAME-Trap primer water connections need shut off valves on plan page P-621 -IPC 606.2
4). SAME-Plan page P-114 shows the water heater in a remote location away from the mop sink, The Relief valve outlet piping can only have 4 fittings per relief valve instructions, Update detail #5 to show relief valve to be discharged to the water heater pan. -IPC 303.2


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov