Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM04989
Parcel: 13355230B

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM04989
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/15/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04989

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
Seems like a new door opening is proposed on the west wall near the north end (room 110) of the building. Please have your EOR address the lateral and gravity load concerns because of this opening.


BUILDING REVIEW COMMENTS:
Denied
1. The occupant load calculations are incorrect. The lounge is an assembly space and not included. Provide a corrected occupant load calculation in accordance with Table 1004.5
2. Based on the updated occupant load calculation, the door between the lounge and clinic is not swinging in the direction of egress. Provide a correctly swing door in accordance with Section 1010.1.2.1.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved


PLUMBING REVIEW COMMENTS:
Denied
E-131 FLOOR PLAN - ETHERNET SYSTEM: No data drops for exam rooms?
E-631 PANEL SCHEDULES: No electrical issues, LCPR may need its feeder and 70 amp CB to be upgraded as it has a calculated 66-amp load.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/21/2022 SSHIELD1 ENGINEERING REVIEW Passed
07/21/2022 STEVE SHIELDS ZONING REVIEW Approved
07/21/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/03/2022 ROBERT SHERRY WATER REVIEW Completed
08/18/2022 JVINCEN1 FIRE REVIEW Reqs Change Resolve building comments

john.vincent@tucsonaz.gov
5203495581

Final Status

Task End Date Reviewer's Name Type of Review Description
08/18/2022 VVERA1 OUT TO CUSTOMER Completed