Permit Number: T22CM04955
Parcel: 140160080

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM04955
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2022 VFLORES1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change Please contact Pima County Addressing to have all unit # added into the system Phone #:520-724-9512 Email: addressing@pima.gov
07/08/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04955

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. The structural narrative for the project contains an incorrect reference to the wrong edition of the IEBC. Correct the incorrect reference.


BUILDING REVIEW COMMENTS:
Denied
1. The occupant load factors used for the lobby and the office are incorrect. While this won't change the O.L. by much however, it needs to be correct. The lobby is a queuing area and the office is a business area. The incorrect occupant load factors have been used. Provide a corrected occupant load calculation.
2. Please provide clarification if the space is protected by a sprinkler system and fire alarm system.
3. Provide clarification on the uses of adjacent tenants. Ensure proper separation between tenants.
4. Additional exit signage maybe required upon inspection.


MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Denied
1. To ensure compliance of the gas line design the Gas type, Inlet pressure, Pressure Drop, and Specific Gravity, also provide a gas load summary, size of all piping (this information is lacking at the piping feeding the fixtures and the amount of BTUs coming in at meter. Please provide more details for the sizing of the gas lines pursuant to Section 402.3.
2. The sink adjacent to the pizza oven could possibly used with grease laden waste. Connect the sink to the grease waste line.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/19/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/02/2022 ROBERT SHERRY WATER REVIEW Completed
08/02/2022 SSHIELD1 ENGINEERING REVIEW Passed
08/02/2022 WBERGER1 ZONING REVIEW Approved PDSD TRANSMITTAL

FROM: Wyatt Berger
Planner

PROJECT: T22CM04955
1770 E Irvington #104
Peter Piper Express (1st Review)

TRANSMITTAL DATE: July 19, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. As you are proposing a new Food Service use, demonstrate that less than 50% of all uses within the existing shopping center are devoted to Food Service and Alcoholic Beverage Service uses to comply with parking standards. If more than 50% of all shopping center uses are Food Service and Alcoholic Beverage Service uses, a development package is required.

If you have any questions about this transmittal, please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov.
08/15/2022 JPEELDA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/15/2022 VVERA1 OUT TO CUSTOMER Completed