Permit Number: T22CM04954
Parcel: 133110190

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM04954
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.

1.Does the scope of work include both interior and exterior lighting? Indicate on the plans and provide inventory (quantity) for the interior or use the ComCheck App.

2.Provide full compliance with the 2018 IECC for the lighting energy requirements. ComCheck is acceptable. Interior and exterior lighting.

3.Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.

4.Provide a complete luminaire schedule. (Indicate shielding)

5. Indicate on the plan whether or not a special inspection is required per sec. 104.2.2, and 106.2.

6.Provide information for Curfew lighting controls If applicable. Exterior unshielded luminaires. Section 403.1, 403.5. Be sure the lighting control timer has standby back-up power as required, 403.5.1.

7. Verify that the lighting in ‘Special Use Areas’ complies with section 701.3, 701.4

Do not confuse the Outdoor Lighting Code with the IECC.

Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/27/2022 NGARCIA3 OUT TO CUSTOMER Completed