Permit Number: T22CM04953
Parcel: 105110660

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM04953
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

Ref; Electrical line diagram, panel schedules.

The previous review comments are not completely addressed.

The line diagram shows panel 'A’ feeding panel ‘B’. The panel schedule for panel ‘A’ shows sub panel F1 not panel ‘B’. Please clarify.

The line diagram shows panel ‘B’ as new. The panel schedule shows panel ‘B’ as existing. Please clarify.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.