Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM04953
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/07/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1 Ref; Plan Sheets E1, E2. The notes under the EQUIPMENT SCHEDULE do not correlate with the panel schedules. See note for the Hood. Also be more specific as to which panels the branch circuits are assigned to. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |