Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T22CM04953
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/14/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/14/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 07/14/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/18/2022 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 07/20/2022 | WBERGER1 | ZONING | REVIEW | Approved | |
| 07/20/2022 | WBERGER1 | ENGINEERING | REVIEW | Passed | |
| 07/20/2022 | WBERGER1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/27/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Ref; Plan Sheet E1, E2. (a) The electrical line diagram shows panel ‘F1’ as new and the panel schedule shows panel ‘F1’ as existing. Please clarify. (b) Show the location of panels ‘F’ and ‘F1’ on the electrical floor plans. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |
| 08/23/2022 | WILDAN | BUILDING-COMMERCIAL | REVIEW | Completed |