Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM04948
Parcel: 141220290

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM04948
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04948

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide Structural Calculations for New Platform Structural Steel members per Section 1601.1 of International Building Code 2018.
2. Verify the Floor Slab adequacy to support the Point Loads from new structural columns supported on existing slabs.
3. Verify the adequacy of Existing Structural Steel Members and Steel Joists to support the new platform loadings.
4. Provide Seismic Calculations for the Building with these additional loadings of new platform per Section 1613 of International Building Code 2018.
5. The steel joists would need reinforcing if the point loads are off panel points. Provide details for the reinforcing.
6. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.

BUILDING REVIEW COMMENTS:
Denied
1. Provide a brief narrative on the extent of the work being completed.
2. Update and provide existing occupant loads.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Denied
1. Sheet E102: Indicate branch circuit number / panelboard for new light fixtures.
2. Sheet E102: Indicate wire size to be used for new lighting and receptacles branch circuits.
3. Sheet E601: Provide voltage drop calculation for new receptacles and lighting branch circuits circuits to comply with 2018 IECC, C405.9.
4. Sheet E102: Show means of egress emergency illumination. 2018 IBC 1008.3 and 1008.3.5.
5. Sheet E102: Show location and controls for light fixtures.


PLUMBING REVIEW COMMENTS:
Conditionally Approved
No Plumbing or gas work shown= N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/19/2022 SSHIELD1 ENGINEERING REVIEW Passed
07/19/2022 STEVE SHIELDS ZONING REVIEW Approved
07/19/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/02/2022 ROBERT SHERRY WATER REVIEW Completed
08/15/2022 JPEELDA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/15/2022 VVERA1 OUT TO CUSTOMER Completed