Permit Number: T22CM04942
Parcel: 14108534A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM04942
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2022 VFLORES1 PIMA COUNTY - ADDRESSING PIMA COUNTY - ADDRESSING Reqs Change Please verify unit # contact Pima County Addressing to have unit 15 added into the system Phone #:520-724-9512 Email: addressing@pima.gov
07/19/2022 WBERGER1 ENGINEERING REVIEW Passed
07/19/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/19/2022 WBERGER1 ZONING REVIEW Approved
08/08/2022 JPEELDA1 FIRE REVIEW Reqs Change Permitting shows City of Phoenix and shall be the COT and Tucson Fire Department for High-Piled Storage
Provide TFD permit number on this design set

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
08/18/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM04942

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Sheet FP1 This Project is located in City of Tucson. Plans to be approved by City of Tucson Fire Department.
Sheet FP1 Remove all references to the City of Phoenix, Provide documents pertaining to the City of Tucson.
Sheet FP1 Provide approval from city of Tucson Fire for this Project.
Sheet FP-02 Provide spacing between required exit doors per IBC And IFC.
Sheet FP-02 Provide exiting plan per IBC Chapter 10. Provide Accessible Path of Travel per ADAAG. for required exit doors.



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2022 NGARCIA3 OUT TO CUSTOMER Completed