Permit Number: T22CM04938
Parcel: 13323371A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM04938
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Keynote 8.5 has not been revised to show the SHGC and U-value requirements for the new window. [Initial comment: Provide energy code compliance calculations for the alteration of the building envelope (e.g. COMcheck). Provide sufficient detail on the drawings to evaluate the energy compliance of the alteration of the building envelope. The information shall, as a minimum, include U-factors and the SHGC for the new window. Reference: Sections C402, C502.1, International Energy Conservation Code 2018.]