Permit Number: T22CM04932
Parcel: 11628001L

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM04932
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Replacement of the five AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The units themselves will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided.
08/19/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM04932

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

THE PLANS ARE REQUIRED TO BE SEALED BYA PROFESSIONAL REGISTRANT PER AAC 4-30-304

PROVIDE AN ECC-ES REPORT FOR THE ROOFING MEMBRANE

PROVIDE A LIST OF THE ADOPTED CODES BYTHE CITYOF TUCSON

PROVIDE A MECHANICAL FLOOR PLAN FOR THE WORK DESCRIBED IN THE CLUBHOUSE HVAC PROJECT GUIDELINES. NEED MECHANICAL ENERGY CONSERVATION CODE COMPLIANCE FOR HVAC EQUIPMENT, DUCT INSULATION, ECONOMIZERS AND PIPE INSULATION. IMC 301.2

PROVIDE AN ELECTRICAL PLAN FOR WORK COVERED UNDER THE NATIONAL ELECTRIC CODE WHICH INVOLVES THE INSTALLATION OR CHANGE-OUT OF DISCONNECTS, RECEPTACLES, WIRING, DETECTORS AND CONTROLS. IMC 301.10.

SUBMIT MECHANICAL EQUIPMENT SPECIFICATIONS, LISTINGS AND WEIGHTS. IBC 107.2.1.



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2022 NGARCIA3 OUT TO CUSTOMER Completed