Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM04921
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/29/2022 | ARUIZ1 | OIP | REVIEW | Reqs Change | COMMENT: The Plan Set shows a line-side tap, Line taps require compliance with NEC 230.46. Update the plans showing a tap enclosure with sufficient space for the tap device, or show a meter socket extension with tap terminals (approved Milbank tapping device) Rather than a tap, reccomend derating of main and appropriate back feed breaker. |