Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM04921
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/29/2022 | RPARSON1 | OIP | REVIEW | Completed | |
| 07/13/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM04921 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Denied Main breaker replacement may not negatively affect the equipment integrity or listing, NEC 110.3. Provide an electrical load calculation if reducing the main breaker rating. PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/13/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |