Permit Number: T22CM04865
Parcel: 13414002M

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM04865
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2022 SSHIELD1 ENGINEERING REVIEW Passed
07/18/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
07/18/2022 STEVE SHIELDS ZONING REVIEW Passed
08/08/2022 JPEELDA1 FIRE REVIEW Approved
08/19/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM04865

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


Sheet G1.0; Accessible ingress is not part of the scope of the review. DMA

Sheet G1.0; Scope of this review is limited based upon the information provided. DMA

Sheet G1.0, 2010 ADA, 2009 A117.1. List codes plans have been in conformance with. DMA

Sheet G1.0; Identify any and/or all Special Inspections required, example; Welding, post installed anchors, etc... and Deferred items. DMA

Sheet G1.0; Plans do not provide any building code data. This limits the scope of the review. DMA

Sheet G2.0, 2010 ADA Section 405; Alteration to ramp requires compliance with this code and section. DMA

Sheet G2.0; The additional occupant load calcs, travel distance and design from the pool served by this exit and the adjacent exit gate has not been provided and are not part of this review. DMA

Sheet G2.0, 2018 IBC Section 1028.5 Exc 4; Confirm safe and unobstructed path of travel from the building in accordance with the condition 4 of the Exception. DMA

Sheet G2.0, 2018 IBC Section 1009.1 (consistent with 2003 IBC as referenced in the 2010 ADA); One accessible means of egress shall be provided, where two means of egress from the accessible portion is required than two means of egress are required. DMA

Sheet G2.0, 2018 IBC Section 1009.2; Continuity of the accessible means of egress is required and shall be continuous to a public way and must consist of one or more of the 10 items listed in this section. DMA

Sheet G2.0, 2018 IBC Section 1017 Table 1017.2; Plans do not provide a complete Building Data analysis, verify compliance with this table. DMA

Sheet X1.1; This is not consistent with note on Sheet G2.0 that identifies ramp as being replaced which would be considered an alteration. DMA

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2022 NGARCIA3 OUT TO CUSTOMER Completed