Permit Number: T22CM04862
Parcel: 14029037D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM04862
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04862
GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Denied
1. the means of egress is required to be illuminated at all times in accordance with 2018 IBC 1008.2. Clarify how the design complies with this regulation (commonly referred to as "night lighting") or indicate why this section would not apply. Occupancy sensors can be used if desired instead of permanently illuminated fixtures.
• 1008.2. Illumination required. The means of egress serving a room or space shall be illuminated at all times that the room or space is occupied.
• 1008.2.1. Illumination level under normal power. the means of egress illumination level shall be not less than 1 footcandle at the walking surface.


PLUMBING REVIEW COMMENTS:
Approved



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
08/08/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/08/2022 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: PDSD Zoning Review Section

PROJECT: T22CM04862 / TI
6363 S Country Club Rd / I-1 Zone (2nd Review)

TRANSMITTAL DATE: August 08,2022

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. This comment was not fully addressed. Zoning acknowledges that the mezzanine has be removed from the plans but under the “PR0JECT NARRATIVE” the mezzanine is still listed. COMMENT: mezzanine addition counts as an addition of square footage to a commercial use and therefor requires an approved development package for the site.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp