Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM04862
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/02/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM04862 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Denied 1. the means of egress is required to be illuminated at all times in accordance with 2018 IBC 1008.2. Clarify how the design complies with this regulation (commonly referred to as "night lighting") or indicate why this section would not apply. Occupancy sensors can be used if desired instead of permanently illuminated fixtures. • 1008.2. Illumination required. The means of egress serving a room or space shall be illuminated at all times that the room or space is occupied. • 1008.2.1. Illumination level under normal power. the means of egress illumination level shall be not less than 1 footcandle at the walking surface. PLUMBING REVIEW COMMENTS: Approved If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 08/08/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/08/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | FROM: PDSD Zoning Review Section PROJECT: T22CM04862 / TI 6363 S Country Club Rd / I-1 Zone (2nd Review) TRANSMITTAL DATE: August 08,2022 Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1. This comment was not fully addressed. Zoning acknowledges that the mezzanine has be removed from the plans but under the “PR0JECT NARRATIVE” the mezzanine is still listed. COMMENT: mezzanine addition counts as an addition of square footage to a commercial use and therefor requires an approved development package for the site. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp |