Permit Number: T22CM04803
Parcel: 126191270

Address:
801 S ERIN AV

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM04803
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2022 RPARSON1 OIP REVIEW Completed
07/05/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04803

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Plans do not include wind uplift calculations. 2018 IRC - 301.1. Provide wind uplift calculations used and verify fastener or ballast type and location.
2. Plans do not include deadload calculations. 2018 IRC - 301.1. Provide structural calculations showing the existing roof system is capable of supporting the additional dead loads of the PV system.


BUILDING REVIEW COMMENTS:
Approved

MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/05/2022 NGARCIA3 OUT TO CUSTOMER Completed