Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM04801
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/08/2022 | STEVE SHIELDS | ZONING | REVIEW | Passed | |
| 07/08/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 07/15/2022 | AWARNER1 | NPPO | REVIEW | Approved | |
| 07/25/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM04801 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Indicate the design criteria on the drawings including the live and dead loads as well as a basic wind speed of 115 mph and a seismic design category B. 2018 IRC table R301.2(1). BUILDING REVIEW COMMENTS: Denied 1. Indicate the required energy requirements on the drawings, only the wall insulation values were found. Windows are required to have a minimum U factor of .40 and a SHGC of .25. The ceiling is required to have a minimum of R30 installed (per the < 500 sf exception). 2018 IECC table R402.1.2. MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: Approved If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |