Permit Number: T22CM04793
Parcel: 13727010A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM04793
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/05/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Needs Review Activity Number: T22CM04793

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. Correct the list of drawing sheet on the cover sheet so it matches the submitted drawings. It appears AD19 may have been replaced with A010, and the electrical sheets are different.
2. Remove the furniture noted SR-1-01 on sheet A821 that is blocking the door of the Provider Retreat room 106 or provide fire egress calculations for this area showing that a door is not needed (or desired).


MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Denied
1. Show the location of all existing or newly installed night lighting, emergency lighting and exit signage on the reflected celling and electrical plans. Include the location of the existing emergency light outside of the egress doors per 1008.3.2.


PLUMBING REVIEW COMMENTS:
Approved

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
07/14/2022 WBERGER1 ENGINEERING REVIEW Passed
07/14/2022 WBERGER1 ZONING REVIEW Approved
07/14/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/27/2022 ROBERT SHERRY WATER REVIEW Completed
08/15/2022 JPEELDA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/15/2022 NGARCIA3 OUT TO CUSTOMER Completed