Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM04792
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/24/2022 | RPARSON1 | OIP | REVIEW | Completed | |
| 07/01/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM04792 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Denied 1. Plans do not include an evaluation from a structural engineer. 2018 IRC - 301.1. Provide structural calculations or a statement of certification from a licensed structural engineer showing the existing roof system is capable of supporting the additional loads of the PV system. BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: N/A ELECTRICAL REVIEW COMMENTS Approved PLUMBING REVIEW COMMENTS: N/A If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/01/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |