Permit Number: T22CM04784
Parcel: 130120830

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM04784
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/24/2022 RPARSON1 OIP REVIEW Completed
07/01/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04784

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Plans do not include deadload calculations reviewed by a licensed structural engineer. 2018 IRC - 301.1. The project involves adding additional loads to an engineered truss system, which requires a structural engineer to evaluate.


BUILDING REVIEW COMMENTS:
Denied
1. Missing information to determine ridge setback. 2018 IFC - 1204.2.1.2. The plans do not show if the PV system takes up more than 33% of the roof area. If more than 33% of area is displaced by the PV system, a minimum 3' setback from the ridge is required.


MECHANICAL REVIEW COMMENTS:
N/A

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
N/A

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
07/01/2022 NGARCIA3 OUT TO CUSTOMER Completed