Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM04765
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/08/2022 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | FROM: PDSD Zoning Review Section PROJECT: T22CM04765 2554 N Treat Av – R-2 Arizona Room Addition (1st Review) TRANSMITTAL DATE: July 7, 2022 Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal. This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10. 1. COMMENT: Review UDC Article 6.4.3 and the lot coverage calculation example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf, and provide a lot coverage calculation on the plan. 2. COMMENT: Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. Provide wall dimensions from design grade to the highest point of each exterior wall of the proposed addition on the elevations so that perimeter yard setback requirements can be determined. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
| 07/12/2022 | AWARNER1 | NPPO | REVIEW | Approved | |
| 07/14/2022 | PCAMARE1 | ENGINEERING | REVIEW | Reqs Change | This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.) Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp. Instructions: • Is this for a new or existing activity application? – Please select New Application. • Submission Type – Select Floodplain Use Permit. • Project Name – Enter a name for your project. • Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided. • Type of Permit – Select Commercial or Residential (Residential is for work on single family residences and duplexes.) • Complete the Applicant Info. • Complete the Contractor, Owner and Architect/Engineer sections as applicable. • Supporting Documentation Upload – Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful. • Sign the application and submit. • You will be given an activity number for your submittal. Please copy and send this number back to us so we can continue the review. |
| 07/22/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Completed | Activity Number: T22CM04765 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Conditionally Approved No mechanical was provided as part of this review ELECTRICAL REVIEW COMMENTS Conditionally Approved 1. Smoke detectors shall be installed in the existing house in each sleeping room, outside of each sleeping room in the immediate vicinity of the bedroom. 2018 IRC R314.2. All smoke detectors shall receive their primary power from the building wiring with a battery backup and shall be interconnected so that the actuation of one alarm will activate all. 2018 IRC R314.4. 2. Carbon monoxide detectors shall be installed in the existing house outside of each sleeping area in the immediate vicinity of the bedrooms. 2018 IRC R315.3. Carbon monoxide devices shall receive their primary power from the building wiring with a battery backup and shall be interconnected so that the actuation of one alarm will activate all. 2018 IRC R314.4. Smoke detectors and carbon monoxide alarms may be combined. 3. Provide an additional receptacle by the window to the west of the new double door where the spacing exceeds the maximum allowed. PLUMBING REVIEW COMMENTS: Conditionally Approved No plumbing work was indicated as part of this submittal If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |