Permit Number: T22CM04751
Parcel: 11006080A

Review Status: Active

Review Details: RESUBMITTAL

Permit Number - T22CM04751
Review Name: RESUBMITTAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/01/2022 ANY BUILDING-COMMERCIAL REVIEW Active
10/12/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

The submitted documents did not meet City of Tucson Plan Submittal Requirements.

Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this code and relevant laws, ordinances, rules and regulations, as determined by the building official. 2018 IBC section 107.2.1.

Provide complete electrical power and lighting plans. Show locations on the floor plans of all replaced and or new electrical devices including Smoke Detectors. Show locations of all replaced and or new luminaires (Light Fixtures) and branch circuit wiring. Provide compliance with NEC for Ground Fault, Arc Fault, protection for all replaced and or new receptacles. NEC 210, 406.12.

It may be necessary to obtain the services of an Arizona Registrant that has experience in preparing plan documents for submittal that meets City of Tucson Plan Submittal Requirements. www.tucsonaz.gov/pdsd.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.