Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM04750
Parcel: 135084630

Address:
1345 S KOLB RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM04750
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/15/2022 SSHIELD1 ENGINEERING REVIEW Reqs Change See Zoning comments
07/15/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/15/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM04750
1345 S Kolb Rd – C-2
Shade Structure (1st Review)

TRANSMITTAL: July 15, 2022
This site is located in C-2 Zone (UDC 4.7.21), Multi-Family is an use is an allowed use in the zone (UDC Table 4.8-4).

1. Per UDC Article 3.3.3.G.2.c A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of the Checklist for Minor Development Changes to Existing Commerical/Industrial Sites must be submitted and approved prior to approval of this building plan. The checklist can be found at: https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf. The DP is a separate submittal from the building plans and is submitted at: https://docs.tucsonaz.gov/Forms/tucsonpermitapp, using Submission Type “Site Review”.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/18/2022 JPEELDA1 FIRE REVIEW Approved
08/13/2022 WILDAN BUILDING-COMMERCIAL REVIEW Reqs Change Activity Number: T22CM04750

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

Denied

Provide certifications for the fire propagation performance and flame spread index requirements of the fabric material. IBC 3105.3
Canopy shall be designed to withstand wind loads and other live loads. IBC 3105.2
Provide list of special inspections and special inspection certificates. IBC 1704 Provide General Structural Notes



If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
08/15/2022 NGARCIA3 OUT TO CUSTOMER Completed