Permit Number: T22CM04747
Parcel: 126160350

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM04747
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2022 STEVE SHIELDS ZONING REVIEW Approved
07/08/2022 SSHIELD1 ENGINEERING REVIEW Passed
07/19/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM04747
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet Zoning and other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

Number each sheet in the plan set.

Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits

SITE PLAN:

1. Show the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Identify any utility lines requiring upgrade or replacement.

FLOOR PLANS:

1. Clarify the fireplace design and show the location on each plan sheet. Show the fireplace as UL-127 compliant, R1004.1 or notate as non-functional.

SECTIONS - DETAILS:

1. Provide a detail and notation identifying the wall and ceiling insulation for minimum code compliance, R106.1.1 & N1102.1.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF.

PLUMBING PLANS:

1. Show all drainage fixtures with connection to the public sewer system, P2602.1. The sink within the building requires connection to the building drain system.

MECHANICAL PLANS:

1. Provide heating facilities in all habitable rooms, R303.9. Show heating (and cooling) system.

ELECTRICAL PLANS:

1. Smoke alarms are required outside each separate sleeping area, R314.3.2. Show a smoke alarm in each bedroom and outside in the immediate vicinity.
2. Clarify the electrical panel space. Panelboards and overcurrent protection devices shall not be in clothes closets, in bathrooms, or over the steps of a stairway, E3405.5 with 36” clear access space, E3405.2.
3. Show the Heat pump circuit size for serving the load, E3702.11.
4. Show all receptacle outlets located within 6’ of a sink with ground fault circuit interrupting protection, E3902.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
07/22/2022 AWARNER1 NPPO REVIEW Approved