Permit Number: T22CM04727
Parcel: 12208064A

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM04727
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2022 STEVE SHIELDS ZONING REVIEW Approved
07/12/2022 AWARNER1 NPPO REVIEW Approved
07/14/2022 PCAMARE1 ENGINEERING REVIEW Approved This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
• Is this for a new or existing activity application? – Please select New Application.

• Submission Type – Select Floodplain Use Permit.

• Project Name – Enter a name for your project.

• Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

• Type of Permit – Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

• Complete the Applicant Info.
• Complete the Contractor, Owner and Architect/Engineer sections as applicable.

• Supporting Documentation Upload – Provide a complete cost estimate for the project. You may also provide additional documents you think will be helpful.

• Sign the application and submit.

• You will be given an activity number for your submittal. Please copy and send this number back to us so we can continue the review.
07/22/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM04688


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Update the design criteria on sheet 1, 2 and 3 to indicate the structure is designed for a basic wind speed of 115 mph and a seismic design category B. 2018 IRC table R301.2(1).
2. Indicate how the new foundation and slab will be tied into the existing house footing. Detail B on sheet 5 shows the slab at the house but there is no reinforcing shown nor slab base. There is no detail for the connection of the new footing to the existing footing structure.
3. Provide a detail for the roof framing that shows how the new roof will be tied into the existing structure, only the new exterior wall is shown on the details.

BUILDING REVIEW COMMENTS:
Denied1. Indicate the required window energy requirements on the drawings. Windows are required to have a minimum U factor of .40 and a SHGC of .25. 2018 IECC table R402.1.2.
2. Provide an existing floor plan of the house and show any windows or doors that will need to be closed to accommodate the new addition. Provide notes or a detail for any infill.

MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Denied1. Note that all new outlets installed in bedrooms, living rooms, family rooms, dens, hallways, and similar areas will be ARC fault protected. 2017 NEC 210.12.
2. Note that a minimum of 90% of all lighting fixtures in the dwelling will contain high-efficacy lamps. 2018 IECC R404.1.
3. Note that all new or replaced 15- and 20-amp outlets shall be tamper proof type. 2017 NEC 210.52.
4. Note on the drawings that all smoke detectors shall receive their primary power from the building wiring with a battery backup and shall be interconnected so that the actuation of one alarm will activate all. 2018 IRC R314.4.
5. Note on the drawings that carbon monoxide devices shall receive their primary power from the building wiring with a battery backup and shall be interconnected so that the actuation of one alarm will activate all. 2018 IRC R314.4. Smoke detectors and carbon monoxide alarms may be combined.


PLUMBING REVIEW COMMENTS:
Denied
1. Correct the plumbing note on sheet 3 to indicate showers and faucets are to not exceed 2.5 gallons a minute, not 3 as noted. Ordinance 7178


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov