Permit Number: T22CM04680
Parcel: 124150270

Address:
807 S EUCLID AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM04680
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2022 WBERGER1 ZONING REVIEW Approved
06/22/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/06/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/06/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/06/2022 ROBERT SHERRY WATER REVIEW Completed
07/13/2022 JVINCEN1 FIRE REVIEW Approved
07/18/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1. Ref; Plan Sheets, AD.2, AD1.0, A1.1. Floor plans and plan notes.

These plans call for relocating electrical equipment, New Electrical, re-installing or re-locating luminaires (light fixtures) including exit fixtures with battery back-up.

Please provide complete electrical power and lighting plans showing all new and or relocated electrical devices, assigned branch circuiting and panel designations, Panel schedules, Load calculations for the “New Electrical”. Plans to be sealed by a registrant registered in the State of Arizona.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.
08/04/2022 JGARCIA1 BUILDING-COMMERCIAL REVIEW Completed
08/11/2022 SCABRAL1 ENGINEERING REVIEW Passed